| home | profile | products | services | EJ guide | tools | literature | contact us |  
   PicoSearch
[ EJ GUIDE]

Post Installation Inspection Prior to System Pressure Test
 

A careful inspection of the entire piping system shall be made with particular emphasis on the following.

bullet

Are the anchors, guides and supports installed in accordance with the system drawings?

bullet

Is the proper expansion joint in the proper location?

bullet

Are the expansion joint flow direction and positioning correct?

bullet

Have all the expansion joint shipping devices been removed?

bullet

Are all guides, pipe supports and the expansion joints free to permit pipe movement?

bullet

If the system has been designed for a gas, and is to be tested with water, have provisions been made for proper support of the additional dead weight load on the piping and expansion joint? Some water may remain in the bellows convolutions after the test. If this is detrimental to the bellows or system operation, means shall be provided to remove such water.

bullet

Has any expansion joint been damaged during handling and installation?

bullet

Is any expansion joint misaligned? This can be determined by measuring the expansion joints' overall length, inspection of the convolution geometry, and checking clearances at critical points on the expansion joint and at other points in the system.

bullet

Are the bellows and other movable portions of expansion joint free of foreign material?

  EJ Guide

 


.
.
.
.

 

= Featured Product =


 
+ View larger images

  Go to featured product archives

U.S. Bellows, Inc. Designed and Fabricated 50 Universal Expansion Joints for an Air Force Base in New Mexico (Ref#91376-A1, EA) 11/14/2007
U.S. Bellows, Inc. fabricated 50 expansion joints from 304L stainless steel. The expansion joints were 6" and 8" sizes. The 6" expansion joints are 24" face to face and the 8" expansion joints are 26" face to face. All of the expansion joints are fabricated with liners that are also made with 304L stainless steel. The design temperature was 200°F and the design pressure was 200 PSIG. The expansion joints were dye-penetrant tested and hydro tested at 300 PSIG. U.S. Bellows, Inc. provides 100% customer satisfaction in terms of quality and delivery.

 

PH: (713) 731-0030          FAX: (713) 731-8640          E-MAIL: info@pipingtech.com

Copyright © 2008  U.S. Bellows, Inc. All Rights Reserved.    Privacy Policy